Important warning
● Before installation and before connecting the cables, the power supply associated with them must be disconnected to ensure safety.
● Installation and wiring must be carried out by qualified technicians inaccordance with the regulations in force.
● The drive must be reliably grounded.
Technical specification
|
model number |
HYV0322-H |
|
norm |
22mm |
|
(electric) cable |
1 metre 5 core |
|
Flow rate (KV) |
4.3 ㎡/hr |
|
Supply Voltage |
220--240VAC 50--60Hz |
|
Maximum closing differential pressure |
1.0bar |
|
Operating temperature |
5--90°C |
|
Auxiliary switching loads |
3A250V |
|
shutdown mode |
AB Off A |
Installation &Operating Procedures
The driver must be removed from the valve body before installation. Ensure that the manual lever is in the (MAN) position and press the square detach button on the bottom side of the drive. Remove the driver from the valve body.
For two-way valves, it must be ensured that the direction of water flow is from A to B of the valve. for three-way valves, it must be ensured that the direction of water flow is from AB to A or from AB to B.
Use the quick-tightening nut and sealing ring supplied with the valve to connect the valve to the pipe. Do not tighten the nut so tightly that the pipe is deformed and the seal leaks.
Ensure that the manual operating lever on the driver is in the (MAN) position Align the flat shaft on the valve body with the drive shaft slot on the driver; then align the round locating pin on the valve body with the locating hole in the driver and press firmly into place. At this point the locking mechanism will snap into place.
Connect the cable plug. Note that the plug and socket catches must be aligned.
The system should be cleaned after the valve has been installed. When cleaning ensure that the manual lever on the actuator is in the (MAN) position
Important warning
Electrical installations must comply with current lEE regulations.Auxiliary switches must be fused with a maximum of 3A to ensure the safety of the internal switch.The drive's control switches must be used with switches that have a contact gap of atleast 3mm to ensure control effectiveness 8,System commissioning: When the system has been flushed out, refilled and fully vented need to follow the steps below to ensure the normal operation of themotorised valve.
(1)Check the drive manual operation handle to ensure it is in the AUTO position.
(2)Switch on the circulating water pump and the boiler, operate the thermostat and check that the opening and closing of the valves can be controlled by thethermostat. lf it can be controlled normally, it means that the installation is correct.
FAQ
Q1: How long is the delivery time for bulk motorized valve orders?
Standard motorized valve orders are usually shipped within 7–20 days, depending on quantity and customization.
Q2: Do you offer 2-way and 3-way motorized valves? What is the difference?
Yes, we offer both. A 2-way motorized valve controls flow in a single direction, while a 3-way motorized valve diverts flow between two different outlets, commonly used in mixing or diverting applications.
Q3. How do I choose the right damper actuator for my project?
Key factors include torque requirements, control signal type (2-position, floating, or modulating), power supply (AC/DC), and whether a spring-return function is necessary. Contact us with your specifications, and our engineers can recommend the most suitable model..
Q4. What materials are your motorized valves made of?
Our motorized valves are available in brass, stainless steel, and PVC to ensure compatibility with different fluids and working environments.
Hot Tags: 22mm closed replace honeywell, China 22mm closed replace honeywell manufacturers, suppliers, factory, Dn25 Normally Closed Replace Honeywell, 28mm Normally Closed Replace Honeywell, Dn20 Closed Replace Honeywell, 22mm Normally Closed Replace Honeywell, motorized zone valve hymh, 22mm Closed Replace Honeywell