NAV SERIES
NAV series electric valve actuator is mainly use with Globe Valve in the HVAC system to regulate the flow of water and steam in response to the demand of a controller.
PRODUCT FEATURE
Complete range from 1000N to 3000N
3 Point floating or Modulating
(0-10VDC or 4-20mA Control Signal Selectable)
Low leakage factor of up to 0.05%
High close-off pressure actuator satisfies demanding requirements of high-rise buildings and high pressure pumping systems
TECHNICAL SPECIFICATION
|
ACTUATING FORCE |
1000N/1800N &3000N |
|
POWER SUPPLY |
AC 24V |
|
FREQUENCY |
50/60 Hz |
|
POWER CONSUMPTION |
II |
|
CONTROL SIGNAL |
See TABLE 1: VALVE CODE NUMBER DESIGNATION |
|
LIFE CYCLE |
60,000 cycle |
|
IP PROTECTION |
IP 42(1000N),IP54(1800N/3000N) |
|
AMBIENT TEMPERATURE |
-20°...50°as per IEC721-3-3 |
|
AMBIENT HUMIDITY |
5..95%rH(non Condensing) |
|
INVENTORY TEMPERATURE |
+70°C as per IEC 721-3-2 |
|
STROKE LENGTH |
Max 20 mm(1000N),Max 42mm(1800N/3000N) |
|
WEIGHT |
See TABLE 2: MAXIMUM CLOSE-OFF PRESSURE (KPA) AND WEIGHT |
|
CERTIFICATION |
CE and ISO 9000 (EN...requirements) |
TABLE 1: VALVE CODE NUMBER DESIGNA TION

|
VALVE ACTUATOR NAV |
NAV = Valve Actuator |
|
POWER SUPPLY |
1 = AC 24 |
|
MODULATING SIGNAL (APPLICABLE FOR MODULATING SIGNAL) |
2 = 0(2)-10 Vdc (Factory Default Setting) / 0(4)-20 mA |
|
ACTUATING FORCE |
10 = 1000N 18 = 1800N 30 = 3000N |
To Order
Specify the code number from the Valve Code Number Selection Guide.
Repair Parts
Available repair parts for NVCF Series Valves include replacement valve bodies and replacement actuators.No other field repairs should be attempted.
TABLE 2: MAXIMUM CLOSE-OFF PRESSURE (KPA) AND WEIGHT
|
TABLE 2: MAXIMUM CLOSE-OFF PRESSURE (KPA) AND WEIGHT |
|||||||
|
MAXIMUM SHUTOFF PRESSURE (KPA) |
WEIGHT |
||||||
|
MODEL |
FORCE (N) |
DN20 |
DN25 |
DN32 |
DN40 |
DN50 |
KG |
|
NAV... - 10 |
500 |
1000 |
680 |
550 |
400 |
270 |
1.2 |
|
MAXIMUM SHUTOFF PRESSURE (KPA) |
WEIGHT |
||||||
|
MODEL |
FORCE (N) |
DN20 |
DN25 |
DN32 |
DN40 |
DN50 |
KG |
|
NAV... - 18 |
1800 |
340 |
150 |
90 |
- |
- |
4.8 |
|
NAV... - 30 |
3000 |
- |
- |
270 |
150 |
90 |
5.0 |
FIGURE 3: ACTUATOR WIRING DIAGRAM

TABLE 3: DIMENSION OF ACTUATOR (mm)

APPLICATION OVERVIEW
The NAV series Electric Valve Actuator features a complete range from 1000N to 3000N actuating force.
They are use with the globe valve to regulate the flow of water or Steam. The Actuator can be ordered with NENUTEC Valve NVCS or NVCF series valves and NTC controller for a complete HVAC solution.
FAQ
Q1: What warranty do you provide for motorized valves?
We provide a standard 12–24 month warranty for our motorized valves, covering manufacturing defects.
Q2: How should I choose the right size and type of motorized valve for my project?
You should consider pipe size, flow rate, working pressure, voltage, and application. Our engineering team can help you select the best motorized valve solution.
Q3. What are the main types of damper actuators?
The main types include electric damper actuators, pneumatic damper actuators, spring return actuators, and non-spring return actuators. The right type depends on your HVAC project requirements and control system.
Q4. Do you offer spring return and non-spring return damper actuators?
Yes.
Spring return actuators automatically return the damper to its safety position in case of power failure, often used in fire and smoke applications.
Non-spring return actuators are ideal for standard ventilation control.
Hot Tags: 3 point control electric globe valve actuator, China 3 point control electric globe valve actuator manufacturers, suppliers, factory, 2 Way Flanged End Globe Val, 2 Way Motorised Zone Valve, valve actuator, Modulating Control Electric Globe Valve Actuator, 3 Way Brass Screwed End Globe Valv, 2 Way Brass Screwed End Globe Valv